Mistral UPS

Check the previous versions
IP Compact

UPS ONLINE MM DOUBLE CONVERSION - 1 to 3 KVA

Use cases

Network Equipment Network Equipment  Banking Institution Banking Institution  Hospitality Hospitality
Data Centers Data Centers Domestic Use Domestic Use Communication systems Communication Systems
Server Rooms Server Rooms Industrial Environment Industrial Environment Workstation Workstation
INdustrial Environment Textile Factories
Automation
Automation    

Perks

  • 1Phase In/1Phase Out UPS

It is 1-Phase In/ 1Phase Out high-density UPS system, of which input current is kept in balance. No unbalance problem might occur. And also support for three phase input.

  • Digital Control

This series UPS is controlled by Digital Signal Processor(DSP); ehance, it increases reliability, performance, self-proteciton, self-diagnostics and so on.

  • Battery Configurable from 2pcs to 20pcs depending on UPS capacity.

The battery voltage of this series UPS can be configured at2pcs, 9pcs, 16pcs or 20pcs according to your convenience.

  • Intelligent Charging Method

The series UPS adopts advanced three-stage charging method:

  1. 1 st stage: high current constant current charging to guarantee to charge back to 90%.
  2. 2 -stage: Constant Voltage in order to vitalize battery and make sure batteries are fully charged.
  3. 3 stage: floating mode, with this 3-stage charging method, it extends the life of the batteries and guarantees fast charging.
  • LCD Display

With LCD plus LED displays, the user may easily get UPS status and its operational parameters, such as input/output voltage, frequency & load%, battery % and ambient temperature, etc..

  • Intelligent Monitoring Function

Via optional SNMP Card, you may remotely control and monitor the UPS.

Description

This UPS series is a kind of single phase in single phase out high frequency online UPS, it provides four (4) capacities: The 1 KVA, the 3 KVA, the 6 KVA and 10   KVA. These equipments are modularized and adopt the N+1 redundancy. It can flexibly increase the number of the UPS modules according to the load capacity which is convenient for flexible allocation and gradually investment.

The UPS can solve most of the power supply problems, such as blackout, over-voltage, under-voltage, voltage sudden drop, oscillating of decreasing extent, high voltage pulse, voltage fluctuation, surge, inrush current, harmonic distortion (THD), noise interference, frequency fluctuation, etc..

This UPS can be applied to different applications from computer device, automatic equipment, communication system to industry equipment.

  • Standards (Surge Suppressions): EN 61000-2-2/ EN 61000-4-2, Level 4/ EN 61000-4-3, Level 3/ EN 61000-4-4, Level 4 (also on signal ports)/ EN 6100-4-5, Level 4 Criteria A

  • Standards (EMC Certification): CE per IEC/EN 62040-2/ Class B                                              

  • Standards (EMC Emissions): IEC 62040-2:ed2:2005 / EN 62040-2:2006

  • Safety conformance: IEC 62040-1-1, IEC 60950-1

  • Agency marking: CE

Products

Carte BMS Modbus optionnelle pour Mistral 6 et 10 KVA

POAIP0301 - Carte BMS Modbus optionnelle pour Mistral 6 et 10 KVA

Mistral 1KVA

POOIP1501 - Mistral 1KVA

  • Type 1(Capacity) : 1 KVA
  • Type 2(Power rating) : 900 W
  • Type 3(Nominal input) : 200/ 208/ 220/ 230/ 240 Vac
  • Type 4(Voltage) : 110~290 Vac
  • Type 5(Frequency) : 45~65 (Auto detect) Hz
  • Type 6(Input power factor) : ≥ 0.98
  • Type 7(Nominal output Voltage) : 200/ 208/ 220/ 230/ 240 Vac
  • Type 8(Output power factor) : 0.9
  • Type 9(Output voltage regulation) : ±2 %
  • Type 10(Crest factor) : 3:1
  • Type 11(Total Harmonic Distortion (THD)) : ≤3 (Linear mode) %
  • Type 12(Total Harmonic Distortion (THD)) : ≤3 (Battery mode) %
  • Type 13(Numer of batteries) : 2 Pcs
  • Type 14(Type of batteries) : 12/ 9 V/ Ah
  • Type 15(Dimension (LxHxP)) : 440 x 86.5 x 430 mm
  • Type 16(Humidity) : 0~90 %
  • Type 17(Operating temperature) : 0~40 °C
  • Type 18(Communication interface) : RS232/ USB Port/ RJ 245/ SNMP card
  • Type 19(Output) : IEC 320 C13-10A x 6
  • Type 20(Dimensions) : 440 X 86.5 X 430 (W X H X D) mm

POOIP1502 - Mistral 2KVA

  • Capacity : 1800 W
  • Type : True Online Double Conversion
  • Input voltage : 200/ 208/ 220/ 230/ 240 ±20% Vac
  • Input frequency range : 45~65 Hz
  • Power Factor : 0.9
  • Crest factor : 3:1
  • Efficiency (Sector mode) : upto 90%
  • Efficiency (Batterymode) : > 85%
  • Efficiency (ECO mode) : > 94%
  • THD (Total Harmonic Distortion) : Less than 3% linear mode
  • THD (Total Harmonic Distortion) : Less than 5% non-linear mode
  • Number of batteries : 4pcs
  • Type of batteries : 12V9Ah
  • Size : 440 X 86,5 X 430 mm
  • Technical specifications : Refer to attached Annex_01
Mistral 3KVA

POOIP1503 - Mistral 3KVA

  • Type1(Nominal Capacity) : 3000 (2700 W) VA
  • Type2(Online Double Conversion) : Type
  • Type3(200/ 208/ 220/ 230/ 240) : Input Voltage Vac
  • Type4(200/ 208/ 220/ 230/ 240) : Output Voltage Vac
  • Type5(45~65 HZ (auto-detection)) : Input Frequency Hz
  • Type6(50/ 60 Hz + 0.02 Hz) : Output Frequency Hz
  • Type7(Yes) : Surge Protection
  • Type8(MTBF (Mean Time Between Transfer)) : 0 Ms
  • Type9(IEC 320 C13-10A x 6 & C19 x 16A x 1 (personalized)) : Output Sockets
  • Type10(VRLA Maintenance Free Batteries (Valve Regulated Lead Acid Batteries)) : 5 Years
  • Type11(Noise level) : 50 at 1 meter dBA
  • Type12(Power Saving Mode & Eco friendly mode) : Environmental Compliance
  • Type14(Audible alarms for voltage fluctuations, frequency, current, overload and any types of fauly conditions. LED indicators - LCD display - Built-in MCB resettable switch) : Features
  • Type15(Heavy Duty 3-pin BS1363 13A input socket) : Main Plug (input)
  • Type 16(Made: Ipower / Model: Mistral 3 KVA Convertible UPS/ EU Standard) : Made/Model
  • Technical specifications : Refer to attached Annex_01
  • Safety and EMC certifications(IEC 62040-1-1, IEC 60950-1) :
  • ISO certification(EN 61000-2-2 EN 61000-4-2, Level 4 EN 61000-4-3, Level 3 EN 61000-4-4, Level 4 (also on signal ports) EN 6100-4-5, Level 4 Criteria A CE per IEC/EN 62040-2, Class B) :
  • EMC (Emissions)(IEC 62040-2:ed2:2005 / EN 62040-2:2006) :
Mistral 6KVA MM sans cabine, sans batteries

POOIP1504 - Mistral 6KVA MM sans cabine, sans batteries

  • Nominal Capacity : 6 KVA
  • Technology : True Online Double Conversion
  • Type3(Input Voltage) : 230V ± 20% (Single phase) Vac
  • Type4(Output Voltage) : 230V ± 3% (Single phase) Vac
  • Type5(Input Power Factor) : ≥ 0.99 @ full load
  • Type6(Output Power Factor) : 0.9
  • Type7(Input Frequency) : 50 Hz ± 5% (Auto-Sensing) Hz
  • Type8(Output Frequency) : 50 Hz ± 1% (Auto-Sensing) Hz
  • Type9(Output Voltage Regulation) : ˂±1%
  • Output Voltage Distortion (THD) : ≤2%
  • Output Voltage Distortion (THD)(Non linear load) : ≤5%
  • Type12(Crest Factor) : 3:1
  • Type13(Overload Capacity (Line Mode)) : ≤110%for 60 mins, ≤125%for 10 mins, ≤150% for 1sec
  • Type14(Bypass) : 0ms MTBF automatic bypass/ Manual Bypass
  • Type16(Noise level) : ˂ 52 dB at 1 meter
  • Type17(Efficiency) : ˃93.5%
  • Type 18(Operating temperature) : 0-40 °C
  • Type19(Relative Humidity) : 0-95% (non condensing)
  • Type23(blackout, over-voltage, under-voltage, voltage sudden drop, oscillating of decreasing extent, high voltage pulse, voltage fluctuation, surge, inrush current, harmonic distortion (THD)...etc -) : Protected against
  • Type24(Built-in lightning protector) : Refer to attached Annex for technical specs Comply
  • Type26(BS 5750 pt: 1987 certification/ replaced by BS EN ISO 9002:1994 since 15 July 1994 (Refer to attached Annex_05 for BS certificates)) : BS 5750 pt: 1987 certification
  • Type28(Designed in France and manufactured in IPOWER`s factories in China) : Make and Country of origin
  • Type29(Self diagnostic function/ auto shutdown & auto restart/ cold start/ fan control speed/ automatic frequency synchronization/ EMI filter/ Hotswappable batteries...etc) : Mistral 6 KVA features
  • Type30(443(W) X 131(H) X 580(D)) : Dimension mm
  • Type31(25) : Net weight Kg
Mistral 10KVA MM

POOIP1505 - Mistral 10KVA MM sans cabine sans batteries

  • Type1(Power rating) : 10 KVA of power factor 0.9
  • Type2(Technology) : True Online Double Conversion
  • Type3(Input Voltage) : 220/ 230/ 240 Vac
  • Type4(Input Voltage Range) : 208 ~ 478 Vac
  • Type5(Rating frequency (auto sensing)) : 45 ~ 55Hz / 54 ~ 66Hz
  • Type6(Input power factor) : ≥ 0.99
  • Type7(Input current distortion (THDI)) : ≤3%(100% linear load,input THDI ≤1%)
  • Type8(Input current distortion (THDI)) : ≤5% (100% non linear load,input THDI ≤1%)
  • Type9(Output rating voltage) : 220 / 230V / 240 Vac
  • Type10(±0.1%) : Output Voltage regulation
  • Type11(±5%) : Dynamic Response
  • Type12(100) : Resistive load %
  • Type13(˂1) : Response time ms
  • Type14(≥90) : Efficiency at normal mode %
  • Type 15(VRLA - Maintenance Free Valve Regulated Sealed Acid Lead of 12V9Ah) : Battery type
  • Type 16(10A) : Charger type A
  • Type17(Refer to attached Annex_01) : Start-on batteries
  • Type 18(Three (03) years of warranty effective from date of commissioning of installed UPS together inclusive of batteries, parts as well as labor) : Warranty

SOCIP0701 - Battery Cabinet Mistral 1K including 4×12V9AH batteries

  • Dimensions(LxHxP) : 440x86.5x430 mm
  • Batteries(4 pcs) : 9 Ah
  • Back up time(Each additional battery provides 40 additional minutes with full load connected to the UPS) :

SOCIP0702 - Battery Cabinet Mistral 2K including 8×12V9AH batteries

Battery Cabinet Mistral 3K including 12×12V9AH batteries

SOCIP0703 - Battery Cabinet Mistral 3K including 12×12V9AH batteries

  • Dimensions(LxHxP) : 440x86.5x696 mm
  • Batteries(12 pcs) : 9 Ah
Battery Cabinet Mistral 6-10KVA vide 20 emplacements pour 7 ou 9Ah

SOCIP0704 - Battery Cabinet Mistral 6-10KVA vide 20 emplacements pour 7 ou 9Ah

  • Type1(12) : Nominal Voltage V
  • Type2(T2) : Terminal type
  • Type3(8.60Ah/ 0.430A - 20hr/ 1.80V/ Cell, 25°C/ 77°F) : Rated capacity
  • Type4(7.98Ah/ 0.78A - 10hr/ 1.80V/ Cell, 25°C/ 77°F) : Rated capacity
  • Type5(7.10Ah/ 1.42A - 5hr/ 1.75V/ Cell, 25°C/ 77°F) : Rated capacity
  • Type6(6.45Ah/ 2.15A - 3hr/ 1.75V/ Cell, 25°C/ 77°F) : Rated capacity
  • Type7(5.96Ah/ 5.96A - 1hr/ 1.60V/ 1.75V/ Cell, 25°C/ 77°F) : Rated capacity
  • Type8(129A -5sc) : Maximum discharge current
  • Type9(Approx 19) : Internal resistance mΩ
  • Type10(Discharge: 15 - 50°C (5 - 122°F)) : Operating temperature range
  • Type11(Charge: 15 - 50°C (5 - 122°F)) : Operating temperature range
  • Type12(Discharge: 15 - 40°C (5 - 104°F)) : Operating temperature range
  • Type13(25 ± 3°C - 77 ± 5°F) : Nominal temperature range
  • Type14(Initial charging current less than 2.58A voltage - 14.4V - 15.0V at 25°C (77°F) temperature. Coefficient -30mV/ °C) : Cycle use
  • Type15(No limit on initial charging current voltage - 13.5V - 13.8V at 25°C (77°F) temperature. Coefficient -20mV/°C) : Standby use
Mini dry contact relay card (Pour AS400) only for mistral 1-3KVA

SOIIP0202 - Mini dry contact relay card (Pour AS400) only for mistral 1-3KVA

Specifications

DESCRIPTION MISTRAL 1 KVA MISTRAL 2 KVA MISTRAL 3 KVA MISTRAL 6 KVA MISTRAL 10 KVA
Capacity 900(W) 1800(W) 2700(W) 5400(W) 9000(W)
INPUT
Input voltage 220/ 230/ 240 Vac ( P+N+T) ±20%
Operating input voltage 120 – 276 Vac
Operating frequency range 45 – 55 Hz/ 54 – 66 Hz ± 0.5 Hz
Input power factor ≥ 0.98 ≥ 0.99
Bypass voltage range Max voltage.: +15% (optional +15%, +10%, +25%) Min voltage.: -45% (optional -15%, -20%, -30%) Protected frequency range: ±10% 220V ± 25% (optional +10%, +15%, +20% ) 230: +20% (optional +10%, +15%) 240: +15% (optional +10%) Min voltage: -45% (optional -20%, -30%)
Bypass frequency range ± 10%
Total Harmonic Distortion (THD) ≤ 3% (Linear mode) ≤5% (Non linear mode) ≤ 3% (100% Linear mode)
Generator input Supported
OUTPUT
Output voltage 220/ 230/ 240 Vac (Adjustable)
Power factor 0.9
Voltage regulation ±2%
Frequency (Online mode) 50 or 60Hz ±1%/ ±2%/ ±4%/ ±5%/ ±10% Rated frequency (optional)
Frequency (Battery mode) ≤5% (Non linear mode) 50/ 60 (±0.1) Hz
Crest factor 3:1
Total Harmonic Distortion (THD) ≤ 2% (Linear mode)/ ≤ 5% (Non linear mode)
Wave form Pure Sinewave
BATTERY
Battery voltage Optional voltage (±96/ ±108/ 120 VDC)
Typical recharge time 6-8 hours ( 90% of full capacity)
Backup time Long run unit depends on the capacity of external batteries. Estimated remaining time displayed on front LCD
Charge current Max current: 10A, charge current can be set according to battery capacity installed
SYSTEM FEATURES
Transfer time Utility to battery: 0ms – Utility to bypass: 0ms
Overload (Linear mode) Load (≤110% last 60min/ ≤125% last 10min/ ≤150% last 1sec/ >150% turn back to bypass mode
Overload (Battery mode) 10A input breaker 15A input breaker 20A input breaker 40A input breaker 60A input breaker
Short circuit Hold whole system
Overheat Line mode: switch to bypass – Backup mode: switch down the UPS immediately
Low battery voltage Alarm and switch OFF
Self diagnostic Upon power ON and software control
Battery Advanced (smart) battery management
Noise suppression Complies with EN62040-2
Audible & visual alarms Line failure, battery low, Overload, system fault
Status Led & LCD display Line mode, backup mode, ECO mode, Bypass mode, Battery low, Battery bad, Overload & UPS fault
Reading on the LCD display Input voltage, Input frequency, Output voltage, Output frequency, Load percentage,Battery voltage, Inner temperature & Remaining battery back-up time
Communication interface USB, RS232, Parallel port, SNMP card, Relay card (optional)
ENVIRONMENT
Operating temperature 0 - 4 0 °C
Storage temperature -25 °C – 55 °C
Humidity range 0 – 95% (non condensing)
Altitude <1500m
Noise level <55dB
PHYSICAL
Dimensions (l x h x p) mm 440x86.5x430   440x86.5x696 443 x 131 x 580 (3U)
Weight (Kg) 12   32 56 62
STANDARDS
Security IEC/ EN62040 – 1 IEC/ EN60950 – 1
EMC IEC/EN62040-2,IEC6100-4-2,IEC6100-4-3,IEC6100-4-4,IEC6100-4-5, IEC6100-4-6,IEC6100-4-8