IP Master Plus UPS

Check the previous versions
IP Master
  • Transport icon
  • E-Medical icon
  • Industry icon
  • Emergency icon
  • Data center icon

Low Frequency IP Master Plus (T/T) Online Double Conversion Uninterruptible Power Supply 10-800 KVA

"More resistant and more robust among all Uninterruptible Power Supplies with a built-in GALVANIC ISOLATING Transformer"

Suitable for:

  • Networking environments, such as server rooms, networking equipments, data centers or VOIP, security syatems, medical equipments, banking institutions, manufacturing industries, automation..

  • Reliability and exceptional durability thanks to its Low-Frequency Technology.

  • High level of protection: Totally isolate connected equipment of all electrical disturbances of the electrical network.

  • IGBT rectifier.

  • Anti-harmonic filter "OPTIONAL".

  • Smart battery management.

  • Stand-Alone integrated smart card.

  • Smart networking communication RS232

  • "OPTIONAL" SNMP card.

  • Built-in isolating transformer for a perfect electricity.

  • An output power factor of 0.9.

  • Energy efficiency up to 95%.

 

  1. Use recommended number of batteries. At -15% voltage, UPS can guarantee maintaining the specified output voltage at rated load without discharging, but cannot guarantee the float charge voltage for the battery.

  2. IEC62040-3(5.2.2): UPS, at rated load, and input rated voltage 380V, without battery charging current.

  3. IEC62040-3 (5.2.2): UPS, at rated load or overload, and input rated voltage 380V, battery equalizing charging at maximum current.

  4. Set up through the special software at the backend.

  5. Factory setting is 380V, 400V or 415V, which can be set through the software.

  6. Factory setting is 50Hz; 60 Hz can be set through the software.

  7. IEC62040-3.

  8. IEC62040-3, including 0-100-0% load transient. Transient recovery time is 20ms, with an accuracy of 1%.

  9. Factory setting is 0.1 Hz/s; 1Hz/s can be set through the software.

Perks

Higher energy efficiency up to 95% and with a built-in Galvanic Isolating Transformer

Description

IP MASTER 10 KVA

IP MASTER 20 KVA

IP MASTER 30 KVA

IP MASTER 40 KVA

IP MASTER 60 KVA

IP MASTER 80 KVA

Capacity

9000(W)

18000(W)

27000(W)

36000(W)

54000(w)

72000(w)

Input

Input voltage

380/ 400/ 415Vac (380-25%, 415+20%), (3-phase+N+E)

Operating input voltage range

±15%, (maxim working range : 290Vac~498Vac)

Frequency

50/ 60Hz (±5Hz)

Input frequency range

45~65 Hz

Power stepping time

5~300 S

Voltage range for inverter

320~490 Vdc

Bypass voltage tolerance

Default upper limit 20% default lower limit-40%

Confirmation time for bypass voltage recovery

2S

Output

Output voltage

380/ 400/ 415 Vac (±1%)

Frequency

50/ 60Hz (±5Hz)

Total Harmonic Distortion (THD)

< 3% (linear load)

Crest factor

3:1 (Max)

Efficiency

89% >90% >91% >92%

Bypass

Nominal voltage

380/ 400/ 415

Nominal frequency

50/ 60 Hz

Battery

Battery voltage

384 vdc

SYSTEM FEATURES Long run unit depends on the capacity of external batteries. Estimated remaining time displayed on front LCD

Transfer time

0ms (Sector mode < - - > Battery mode)

Overload

110%/ 60 min, 125%(10mins, 150% 1 min

Interface

LCD, LED indicator, SNMP adaptor, dry relay, RS232, RS485, SNMP card (optional)

Optional

Anti-harmonic filter, SNMP adaptor, LBS cable, battery thermometer, Bypass current sharing indicator

Environment

Operating temperature

0 – 40°C

Stocking temperature

-25°C - 55°C

Humidity

0 – 95% (non condensing)

Altitude

< 1500m

Volume

60dB < 65dB

Dimensions (W x H x D) mm

 

570 X 800 X 1198

Standards

Security

IEC60950-1,IEC62040-1-1 IEC/EN62040-2 IEC62040-3 IP20 standards

EMC

IEC/EN62040-2,IEC6100-4-2,IEC6100-4-3,IEC6100-4-4,IEC6100-4-5, IEC6100-4-6,IEC6100-4-8

Description

IP MASTER 100 KVA

IP MASTER 120 KVA

IP MASTER 160 KVA

IP MASTER 200 KVA

IP MASTER 300 KVA

IP MASTER 400 KVA

Input

Input voltage

380/ 400/ 415Vac (380-25%, 415+20%), (3-phase+N+E)

Operating input voltage range

±15%, (maxim working range : 290Vac~498Vac)

Frequency

50/ 60Hz (±5Hz)

Input frequency range

45~65 Hz

Power stepping time

5~300 S

Voltage range for inverter

320~490 Vdc

Bypass voltage tolerance

Default upper limit 20% default lower limit-40%

Confirmation time for bypass voltage recovery

2S

Output

Output voltage

380/ 400/ 415 Vac (±1%)

Frequency

50/ 60Hz (±5Hz)

(Max) output current

152A

182A

243A

304A

456A

608A

Total Harmonic Distortion (THD)

< 2% (linear load)

Crest factor

3:1 (Max)

Efficiency

>92%

>92%

>92%

>92.5%

>93%

>94%

Bypass

Nominal voltage

380/ 400/ 415

Nominal frequency

50/ 60 Hz (auto sensing)

Battery

Battery voltage

384 vdc

SYSTEM FEATURES Long run unit depends on the capacity of external batteries. Estimated remaining time displayed on front LCD

Transfer time

0ms (Sector mode < - - > Battery mode)

Overload

110%/ 60 min, 125%(10mins, 150% 1 min

Interface

LCD, LED indicator, SNMP adaptor, dry relay, RS232, RS485, SNMP card (optional)

Optional

Anti-harmonic filter, SNMP adaptor, LBS cable, battery thermometer, Bypass current sharing indicator

Environment

Operating temperature

0 – 40°C

Stocking temperature

-25°C - 55°C

Humidity

0 – 95% (non condensing)

Altitude

< 1500m

Volume

60dB < 65dB

Dimensions (W x H x D) mm

 

1160 X 805 X 1600 (6P)

1400 X 945 X 1900 (6P)

1640 X 1040 X 1900 (6P)

 

1520 X 830 X 1600 (12P)

1640 X 1040 X 1900 (12P)

1760 X 1040 X 1900 (12P)

Standards

Security

IEC60950-1,IEC62040-1-1 IEC/EN62040-2 IEC62040-3 IP20 standards

EMC

IEC/EN62040-2,IEC6100-4-2,IEC6100-4-3,IEC6100-4-4,IEC6100-4-5, IEC6100-4-6,IEC6100-4-8